Using the Thermal Cycle CAD and what it assumes — 11 / 12

Changing the working fluid: a refrigerator's cycle and a gas turbine's Brayton cycle

Switching the working fluid to the refrigerant R134a, this part calculates the vapour-compression refrigeration cycle of refrigerators and air conditioners (COP 3.27). It explains how heat is carried from a low temperature to a high one and the COP used instead of an efficiency, and introduces gas turbines running on air (the Brayton cycle) and calculations with compressor and turbine maps.

Thermal cycles are not only for power. Refrigerators and air conditioners also carry heat by circulating a working fluid (a refrigerant) round a ring. Where a power plant “makes work from heat”, a refrigerator “uses work to pump heat out of a cold place and throw it away in a warm place”.

Besides water and steam, the Thermal Cycle CAD's working fluid can be air or the refrigerant R134a. This part calculates the R134a refrigerator of the tutorial “Vapour-compression refrigeration”.

Evaporator (saturated vapour out) → compressor (isentropic efficiency 0.8, driven by a 0.9 motor) → condenser (1.0 MPa, saturated liquid out) → expansion valve (→ 0.2 MPa) → evaporator. Refrigerant flow 0.1 kg/s.

## Drying sweat feels cool
Wind on sweaty skin feels cool, because sweat (a liquid) takes heat from the skin as it evaporates into a gas.

The same happens in a refrigerator's evaporator. At low pressure the refrigerant boils even at −10 °C, so it takes heat from the air inside and evaporates. The compressor squeezes the evaporated refrigerant, raising its pressure and temperature above that of the room. The back or sides of a refrigerator feel warm because the condenser there throws the heat brought from inside into the room. Finally the expansion valve (a narrow tube) lowers the pressure, the refrigerant becomes cold again and returns to the evaporator.

## “Gets hot” and “gets cold”
Pumping up a bicycle tyre warms the pump's barrel (squeezing a gas raises its temperature). Spraying an aerosol can for a while makes the can cold (lowering the pressure lowers the temperature). A refrigeration cycle uses the two in turn.

## Choosing the working fluid
Press an empty spot of the canvas and choose under “Working fluid” in “Calculation conditions (whole cycle)”. The machines available depend on the fluid.
Working fluid — Typical use — Notes on machines
water / steam — Rankine cycles (steam-turbine power plants) — cooling water and the detailed condenser are for water only
air — Brayton cycles (the air-standard cycle of gas turbines) — it does not condense, so no condenser; the combustor is a heater, exhaust and intake a cooler
R134a — refrigerators, air conditioners, heat pumps — the condenser is the simple condenser, the evaporator the “Evaporator” block
## Placing the refrigerator
1. Place it with “📘 Tutorials” in the toolbar → “Vapour-compression refrigeration” → “Place on the canvas”. The working fluid becomes R134a automatically.
2. Select the machines to see their settings: the compressor (isentropic efficiency 0.8), the condenser block used as the condenser (condensing pressure 1.0 MPa, subcooling 0), the throttle valve used as the expansion valve (outlet pressure 0.2 MPa), and the evaporator (outlet state given by “Outlet quality” 1.0).
3. A dashed line runs from the motor's “Shaft” to the compressor's “Shaft”: the motor turns the compressor and uses electricity to do so.
4. Press “▶ Calculate”.

## The refrigerator's results
State point — Temperature — State
① evaporator outlet, compressor inlet (0.2 MPa) — −10.08 °C — saturated vapour
② compressor outlet (1.0 MPa) — 53.40 °C — superheated vapour
③ condenser outlet — 39.39 °C — saturated liquid
④ expansion valve outlet (0.2 MPa) — −10.08 °C — wet vapour (quality 0.334)Indicator — Value
Refrigeration effect (heat the refrigerant receives in the evaporator) — 13.71 kW
Heat thrown away in the condenser — 17.90 kW
Compressor shaft power, motor electric input — 4.19 kW, 4.66 kW
COP (cooling, on shaft power) — 3.27
COP (heating, on shaft power) — 4.27 (= cooling + 1)
COP (cooling, on electric input) — 2.94
## What the results tell you
- COP replaces efficiency: a refrigeration cycle uses work to carry heat, so its net output is negative. It is judged not by an efficiency but by “heat removed ÷ power used” (the coefficient of performance, COP). A COP of 3.27 means 4.19 kW of power carries 13.71 kW — about three times the power — out of the cold space. (The efficiency is “not defined” and not shown.)
- Heating COP = cooling COP + 1: the heat thrown away in the condenser is the heat received in the evaporator plus the compressor's power (17.90 = 13.71 + 4.19). An air conditioner heating a room (a heat pump) uses this thrown-away heat for heating.
- The expansion valve keeps the specific enthalpy: it is the same before and after the valve, but the pressure falls, part of the liquid evaporates and the refrigerant cools to −10 °C (quality 0.334).

## Gas turbines running on air (the Brayton cycle)
With air as the working fluid you can calculate the Brayton cycle, the basic form of a gas turbine. In the tutorial “Brayton: the basic gas turbine” (air 10 kg/s, pressure ratio 10, turbine inlet 1400 K, compressor 0.85, turbine 0.88) the cycle efficiency is 33.1 % and the back work ratio 53 %. Unlike a Rankine cycle's pump, the compressor that squeezes the air uses more than half of the turbine's work (a gas takes up a lot of volume). A pressure ratio of 20 raises the efficiency to 36.7 %. A dashed line also joins the turbine's shaft to the compressor's shaft (the turbine drives the compressor directly).

## Off-design operation and maps
Every example so far has given the machines constant efficiencies. Real compressors and turbines change their efficiency and flow when the outside temperature or the load (the output) changes. To calculate such off-design operation, give the compressor and turbine maps (tables of flow, pressure ratio and efficiency for each speed) and choose the calculation purpose “Operating point from maps”. A public general-purpose map (the NASA T-MATS example) can be used, scaled to the design point. See compressor and turbine maps and the gas turbine series.

## Assumptions
- Properties: air and R134a use CoolProp 8.0.0's equations of state (HEOS). Air is treated as a pure substance of fixed composition; changes of composition by combustion are not calculated (gas turbines are represented as air-standard cycles).
- Enthalpy reference differs per fluid: specific enthalpy and entropy follow CoolProp's default reference, so do not compare values between results with different fluids (differences can be compared).
- Refrigeration indicators: the refrigeration effect is the evaporator's heat uptake and is not counted as heat input. COP (cooling) = refrigeration effect ÷ net shaft power consumed; COP (heating) = heat rejected ÷ the same power. With a motor connected, COPs on electric input are given too.
- Wet compression warning: a warning is given when the compressor's inlet contains liquid (here it is saturated vapour, just dry).

## The COPs
\mathrm{COP}_{\mathrm{cooling}} = \frac{Q_{\mathrm{evaporator}}}{W_{\mathrm{compressor}}} = \frac{13.71}{4.19} = 3.27, \qquad \mathrm{COP}_{\mathrm{heating}} = \frac{Q_{\mathrm{condenser}}}{W_{\mathrm{compressor}}} = \mathrm{COP}_{\mathrm{cooling}} + 1

Shared result: an R134a refrigeration cycle (opens without an account or login)

## How to read a shared result
The link opens the calculated flowsheet as it was (no account or login needed; viewing never recalculates).

- Select a block to see its results and its input conditions on the right (below on a phone).
- The cells of the result tables are painted as entered values (blue, marked “entered”) or calculated values (green). Use the colours to see what was given and what was found.
- Each block shows its own (type) name in large letters and, below it in smaller letters, the name given in this article.
- You can move blocks, but nothing is saved. To change conditions and calculate, build the same flowsheet in your own CAD (sign-up and login required).

## What to try next
- Set the expansion valve's outlet (the evaporating pressure) to 0.25 MPa: what is the COP? (3.90 in the tutorial.)
- Lower the condenser pressure to 0.8 MPa: how does the COP change?

- The numbers are calculated with Laplaxian's engine (TESPy 0.11.3, CoolProp 8.0.0; R134a and air by CoolProp's HEOS). The conditions are chosen for explanation; they are not recommended or standard values.