Using the Thermal Cycle CAD and what it assumes — 10 / 12

Reheat and regeneration: heating the feedwater with bled steam

Adding reheat (back to 500 °C at 2 MPa) and an open feedwater heater fed by steam bled at 0.5 MPa to the simple Rankine cycle raises the efficiency from 36.07 % to 40.59 %. The part explains how the splitter and merge blocks are placed and set, why the bleed flow comes out as a result, and why the efficiency rises.

Large steam-turbine power plants add two improvements to the simple Rankine cycle to raise its efficiency.

- Reheat: steam that has expanded and cooled in a high-pressure turbine goes back to the boiler to be heated again, and expands the rest of the way in another turbine.
- Regeneration (feedwater heating): some steam is drawn off part-way through the turbines (bled) and warms the cold water returning to the boiler (the feedwater).

The flowsheet of this part is the tutorial “Reheat and regenerative Rankine” (“📘 Tutorials” in the toolbar); the boiler and condenser conditions and the efficiencies are those of the simple Rankine cycle. There are now ten machines, but taken one at a time they are combinations you have already met.

Boiler (10 MPa, 500 °C) → HP turbine (→ 2 MPa) → reheater (500 °C) → IP turbine (→ 0.5 MPa) → bleed splitter → LP turbine → condenser (10 kPa) → condensate pump → open feedwater heater (merging with the bleed, saturated liquid out) → feed pump → boiler

## Boiling from hot water is quicker
Boiling a kettle from a flask of hot water takes less gas than boiling it from cold tap water.

Regeneration in a power plant does this “start from hot water” with turbine steam. Some steam that has already done some work in the turbine is drawn off and mixed into the cold water returning to the boiler to warm it. That steam hands the feedwater heat that would otherwise have gone to the condenser and been thrown away into the cooling water. Less heat is thrown away, so the efficiency rises.

## Reheat is “warming up again on the way”
On a long walk, a rest half-way lets you finish the walk in good shape. Reheat sends the steam back to the boiler part-way through the turbines to be heated again, so the steam that finally leaves for the condenser is not too wet (does not carry too many droplets).

## How it is used
Placing it from the tutorial and selecting each machine to look at its settings is a good start. When you build it yourself, three points matter.

1. Split the turbine into stages: place three turbines — HP, IP and LP — and give the HP turbine an exhaust pressure of 2 MPa and the IP turbine 0.5 MPa. The LP turbine's outlet is fixed by the condenser's 10 kPa, so it gets none (one per pressure region, part 3).
2. Place the reheater: give the “Reheater” block (inside, the same as the boiler / heater) an outlet temperature of 500 °C. No pressure: it is in the same pressure region as the HP turbine's outlet, so it is 2 MPa.
3. Connect the splitter and the merge: join the IP turbine's outlet to the “Splitter (bleed)” inlet; join the splitter's “Out 1” to the LP turbine and “Out 2” to “In 2” of the “Merge / open feedwater heater”. The condensate pump's outlet goes to the merge's “In 1”. Turn on the merge's “Outlet is saturated liquid (open feedwater heater, deaerator)”. Leave the splitter's fractions empty.

Turning on “Outlet is saturated liquid” adds one condition: “the merged water is just at the temperature where it would start to boil (151.8 °C at 0.5 MPa)”. With the split fraction left empty instead, the bleed flow that meets that condition comes out as an answer. Entering a fraction as well would fix the same amount with two conditions — one condition too many.

## Compared with the simple Rankine cycle (both 10 kg/s at the boiler outlet)
— Simple Rankine — Reheat and regeneration
Cycle efficiency — 36.07 % — 40.59 %
Net shaft output — 11.434 MW — 13.045 MW
Heat input — 31.698 MW — 32.139 MW (boiler 27.209 + reheat 4.930)
Heat thrown away in the condenser — 20.264 MW — 19.094 MW
Water temperature entering the boiler — 46.96 °C — 153.74 °C
Turbine exhaust quality — 0.847 — 0.944
Bleed flow — — — 1.545 kg/s (15.4 %)
## What the results tell you
- What reheat does: heating the steam again at the HP turbine's outlet (2 MPa) raises the quality of the steam finally leaving for the condenser from 0.847 to 0.944 (fewer droplets are kinder to the turbine blades). The output rises too.
- What regeneration does: the 0.5 MPa bleed warms the feedwater to 151.8 °C, so the boiler heats water from 153.74 °C instead of 46.96 °C. The boiler no longer has to supply the heat for warming the cold water; the bleed steam's heat, which would have been thrown away in the condenser, does it instead.
- The bleed flow is an answer: the saturated-liquid condition of the merge gives a bleed of 1.545 kg/s (15.4 % of the boiler outlet flow). Less steam goes through the LP turbine, so its work falls slightly; the overall efficiency still rises.
- On the diagram: on the T–s diagram the boiler line starts at a higher temperature than in the simple cycle, and the turbine line is drawn in two parts because of the reheat.

## Assumptions
- An open feedwater heater is a merge: a heater in which the bleed and the feedwater mix directly is represented by the merge block (with the saturated-liquid outlet condition). A “closed feedwater heater”, which passes heat through tube walls without mixing, is represented by the two-fluid heat exchanger.
- Split fractions: with n outlets, up to n − 1 fractions are given, or replaced by alternative conditions (here the merge's saturated-liquid condition). The last outlet takes the rest.
- The reheater is the boiler model: it is treated like the boiler for heat input targets, fuel heat input and capacity checks; it has its own name only to be told apart in the block list and the results.
- Pressure regions: HP turbine outlet – reheater – IP turbine inlet is one region, whose pressure is set by the HP turbine's outlet pressure (2 MPa) alone.
- Two pumps: the open feedwater heater works at 0.5 MPa, so one pump runs from the condenser to the heater (10 kPa → 0.5 MPa) and another from the heater to the boiler (0.5 → 10 MPa).

## The bleed fraction
From the energy balance of the merge (the flow-weighted average of the two incoming flows' specific enthalpies equals the saturated liquid's),
y = \frac{h_{\mathrm{sat}} - h_{\mathrm{condensate}}}{h_{\mathrm{bleed}} - h_{\mathrm{condensate}}}
(y is the bleed fraction). The Thermal Cycle CAD solves this together with the equations of the whole cycle.

Shared result: reheat and regeneration (opens without an account or login)

## How to read a shared result
The link opens the calculated flowsheet as it was (no account or login needed; viewing never recalculates).

- Select a block to see its results and its input conditions on the right (below on a phone).
- The cells of the result tables are painted as entered values (blue, marked “entered”) or calculated values (green). Use the colours to see what was given and what was found.
- Each block shows its own (type) name in large letters and, below it in smaller letters, the name given in this article.
- You can move blocks, but nothing is saved. To change conditions and calculate, build the same flowsheet in your own CAD (sign-up and login required).

## What to try next
- Set the IP turbine's outlet (the bleed pressure) to 1 MPa: how do the bleed flow and the efficiency change?
- On the T–s diagram, see where the heating line starts compared with the simple cycle.

- The numbers are calculated with Laplaxian's engine (TESPy 0.11.3, CoolProp 8.0.0; water and steam by IAPWS-IF97). The conditions are chosen for explanation; they are not recommended or standard values.

Changing the working fluid: a refrigerator's cycle and a gas turbine's Brayton cycle